Programming 52
E1-05 Maximum Output Voltage
Setting Range: 0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 230.0V (240V Models)
480.0V (480V Models)
E1-06 Base Frequency
Setting Range: 0.0 to 400.0 Hz
Factory Default: 60.0 Hz
E1-07 Mid Output Frequency A
Setting Range: 0.0 to 400.0 Hz
Factory Default: 3.0 Hz
E1-08 Mid Output Voltage A
Setting Range: 0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 12.6V (240V Models)
25.2V (480V Models)
E1-09 Minimum Output Frequency
Setting Range: 0.0 to 400.0 Hz
Factory Default: 0.5 Hz
E1-10 Minimum Output Voltage
Setting Range: 0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 2.3V (240V Models)
4.6V (480V Models)
E1-11 Mid Output Frequency B
Setting Range: 0.0 to 400.0 Hz
Factory Default: 0.0 Hz
E1-12 Mid Output Voltage B
E1-13 Base Voltage
Setting Range: 0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 0.0V (240V Models)
0.0V (480V Models)