o2-12 Fault Trace / Fault History Clear Function
The operator can clear the Fault Trace (U2) and Fault History logs by setting o2-12 = “1: Enabled”. Clearing the Fault Trace and Fault
History logs erases all the information.
o2-14 kWh User Monitor Initialization
The kWh monitors (U1-29 and U1-30) track the power usage of the iQpump drive and are not reset by powering down the drive. To reset
the monitors back to zero, set o2-14 = “1: Clear all”.
Setting Description
0 Disabled (No Effect) (factory default)
1 Enabled
Setting Description
0 Disabled (No Change) (factory default)
1Clear All