As a safety precaution the drive will not respond to a change in the run command when the digital
operator is being used to set or adjust parameters.This parameter will allow the drive to accept or
reject a change in the run command when the digital operator is being used to change or adjust param-
eters. <1110>
Table 1:
B2 DC Braking
Setting Range: 0.0 to 10.0Hz
Factory Default: 0.5Hz
Sets the frequency at which DC injection braking (or initial excitation for flux vector control) starts, in
units of 0.1 Hz. When B2-01 < E1-09, DC injection braking starts from the minimum frequency refer-
ence (E1-09).
Setting Range: 0 to 100%
Factory Default: 50%
DC injection braking current is set as a percentage of inverter rated current. In flux vector control
mode, initial excitation is performed according to the motor no-load current set in E2-03. This param-
eter should not be set unnecessarily high or motor overexcitation may occur.
B1-08 Run Command Acceptance During Programming RUN CMD at PRG
A A A A
Setting Description
0 Run command is disabled when drive is in the programming mode. (factory default)
1 Run command is enabled when the drive is in the program mode
B2-01 DC Braking Frequency (Zero Speed Level) DCInj Start Freq
B B B B
B2-02 DC Braking Current DCInj Current
B B B -
Figure 5 DC Injection Braking at Starting
B2-01
DC Injection
B2-03
DC Injection Braking
Time at Start
Braking Frequency
Section B: Application Parameters
B2 DC Braking