VS-616G5 Programming Manual 77
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
· 3-Wire Control (setting: “0”)
When H1-__ is set to “0”, 3-wire control is enabled. The terminal set to “0” becomes the FWD/REV
run command.
12 Forward Jog √ √ √ √
13 Reverse Jog √ √ √ √
14 Fault Reset (factory default, H1-02) √ √ √ √
15 Fast-Stop √ √ √ √
16 Motor 2 Select √ √ √ √
17 Fast-Stop (Closed, motor decels by C1-09)
<1110>
√ √ √ √
18 Timer Function √ √ √ √
19 PID Disable √ √ √ √
1A Multi-Accel/Decel 2 √ √ √ √
1B Program Lockout √ √ √ √
1C Trim Control Increase √ √ √ √
1D Trim Control Decrease √ √ √ √
1E Reference Sample Hold √ √ √ √
1F Terminal 13/14 Switch √ √ √ √
20-2F External Fault (factory default, H1-01) √ √ √ √
30 Closed: PID Integral is Reset √ √ √ √
31 Closed: PID Integral Value is Held <1110> √ √ √ √
60 DC Injection Activate √ √ √ √
61 Speed Search 1 √ − √ −
62 Speed Search 2 √ − √ −
63 Energy Saving Command √ √ − −
64 Speed Search 3 √ √ √ √
65 KEB Ridethrough N.C. √ √ √ √
66 KEB Ridethrough N.O √ √ √ √
71 Speed/Torque Control Change − − − √
72 Zero Servo Command − − − √
77 ASR Gain Switch − − − √
H1-01
to 6
Setting
Function
Control Method (A1-02)
Reference
PageV/f V/f w/ PG
Open Loop
Vector
Flux Vector
Figure 31 Terminal Function at 3-Wire Sequence Selection (H1-__ = “0”)
S1
S2
SC
Run Command
(Run when “Closed”)
Stop Command
(Stop when “Open”)
FWD/REV Run Selection
(FWD Run when “Open”
REV Run when “Closed”)
S3
Section H: Control Circuit Terminals
H1 Digital Inputs