VS-616G5 Programming Manual 55
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
Custom V/f Pattern
Set up a custom V/f pattern by setting parameter E1-03 to “F”, and then setting the values in parame-
ters E1-04 to E1-13.
* For 460V class units, the value is twice that of 230V class units. For 575V class units the value is 2.5 times the 230V value.
Increasing the voltage in the V/f pattern increases motor torque. However, when setting a custom
V/f pattern, increase the voltage gradually while monitoring the motor current, to prevent:
· Inverter fault trips as a result of motor overexcitation
· Motor overheat or excessive vibration
E1-04 Maximum Frequency Max Frequency
Q Q Q Q
E1-05 Maximum Voltage Max Voltage
Q Q Q Q
E1-06 Motor Base Frequency Base Frequency
Q Q Q Q
E1-07 Middle Output Frequency A Mid Frequency A
Q Q A
E1-08 Middle Output Voltage A Mid Voltage A
Q Q A
E1-09 Minimum Output Frequency Min Frequency
Q Q Q A
E1-10 Minimum Output Voltage Min Voltage
Q Q A
E1-11 Middle Output Frequency B Mid Frequency B
A A A A
E1-12 Middle Output Voltage B Mid Voltage B
A A A A
E1-13 Motor Base Voltage Base Voltage
A A Q Q
Be sure to satisfy the following conditions for setting
parameters E1-04 to E1-13:
E1-09 E1-07 E1-06 E1-11 E1-04
0
Fmin
Fmid A
Fbase Fmax
Frequency
Voltage
E1-10 Vmin
E1-08 V mid A
E1-05 Vmax
Figure 28 Custom V/f Pattern Setting
E1-13 Vbase
FmidB
E1-12 VmidB
Min
MidA
Base
MidB
Max
E1-09 E1-07
E1-06 E1-11 E1-04
Section E: Motor Parameters
E1 V/F Pattern