VS-616G5 Programming Manual 69
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
Setting Range: 0.00 to 2.50
Factory Default: 1.00
Sets the channel 1 output gain for the analog output monitors. To obtain the output level, multiply the
monitor output level by the gain value set in F4-02.
18 Motor secondary current (Iq) Monitors the calculated value of the motors secondary current. (Iq) The motors
rated secondary current corresponds to 100%. 10 V=Rated secondary current.
(0 to + 10 V output)
19 Motor excitation current (Id) Monitors the calculated value of the motors excitation current. (Id) The motors
rated excitation current corresponds to 100%. 10 V=Rated excitation current. (0
to + 10 V output).
20 SFS output frequency Monitors the output frequency after a soft start. This is the frequency without the
correction from compensation functions such as slip compensation. 10 V=Max.
frequency (0 to +/- 10 V possible)
21 ASR input Monitors the input to the speed control loop. The max. frequency corresponds to
100%. 10 V=Max. frequency (0 to +/- 10 V possible)
22 ASR output Monitors the output from the speed control loop. Analog monitor becomes 10 V/
max. output frequency with V/F control. In vector control the analog monitor be-
comes 10V= motor rated excitation current. (0 to +/-10V possible.)
23 Speed deviation Monitors the speed deviation within the speed control loop. The max. frequency
corresponds to 100%. 10 V=Max. frequency (0 to +/-10 V possible.)
24 PID feedback Monitors the feedback value when the PID control is utilized. The input for the
max. frequency corresponds to 100%. 10 V= Max frequency.
(0 to +/-10 V possible.)
25 Not Used --
26 Voltage reference (Vq output) Monitors the inverters internal voltage reference value for the motors secondary
current control. 10 V= 200,400 or 575 VAC (0 to =/- 10 V possible.)
27 Voltage reference (Vd output) Monitors the inverters internal voltage reference value for the motors excitation
current control. 10 V= 200,400 or 575 VAC (0 to =/- 10 V possible.)
28-30 Not Used --
31 Not Used --
32 ACR(q) Output Monitors current control output value for the motors secondary current.
10 V= 100%.
33 ACR(d) Output Monitors current control output value for the motors excitation current.
10 V= 100%.
34-35 Not Used --
36 PID Input Monitor Monitors the input to the PID circuit. This is the PID reference + the PID reference
bias - the PID feedback. 10 V= Max frequency.
37 PID Output Monitor Monitors the output of the PID circuit. 10 V= Max frequency.
38 PID Setpoint or Reference Monitors the PID setpoint. This is the PID setpoint + the PID setpoint bias.
10 V= Max frequency.
F4-02 Analog Output Channel 1 Gain AO CH1 Gain
A A A A
Analog Output Channel 1 Selection (Continued)
F4-01 Setting Function Description
Section F: Option Parameters
F4 AO-08/AO-12 Option Set-up