Sequence Timers 2 to 4
These timers operate identically to Sequence Timer 1. Parameters S2-06 to S2-20 configure Sequence Timers 2 to 4.
Priority
If multiple sequence timers overlap, the timer with the lowest number has priority.
Sequence Timer 1 = highest priority
Sequence Timer 4 = lowest priority
n
S2-01/S2-06/S2-11/S2-16: Sequence Timers 1 to 4 Start Time
Sets the start times for timers 1 to 4. The values must be set less than or equal to S2-02/S2-07/S2-12/S2-17.
No. Name Setting Range Default
S2-01 Sequence Timer 1 Start Time 00:00 to 24:00 00:00
S2-06 Sequence Timer 2 Start Time 00:00 to 24:00 00:00
S2-11 Sequence Timer 3 Start Time 00:00 to 24:00 00:00
S2-16 Sequence Timer 4 Start Time 00:00 to 24:00 00:00
n
S2-02/S2-07/S2-12/S2-17: Sequence Timers 1 to 4 Stop Time
Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.
No. Name Setting Range Default
S2-02 Sequence Timer 1 Stop Time 00:00 to 24:00 00:00
S2-07 Sequence Timer 2 Stop Time 00:00 to 24:00 00:00
S2-12 Sequence Timer 3 Stop Time 00:00 to 24:00 00:00
S2-17 Sequence Timer 4 Stop Time 00:00 to 24:00 00:00
n
S2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day Selection
Sets the days for which sequence timers 1 to 4 are active.
No. Name Setting Range Default
S2-03 Sequence Timer 1 Day Selection 0 to 10 0
S2-08 Sequence Timer 2 Day Selection 0 to 10 0
S2-13 Sequence Timer 3 Day Selection 0 to 10 0
S2-18 Sequence Timer 4 Day Selection 0 to 10 0
Setting 0: Timer Disabled
Setting 1: Daily
Setting 2: Mon - Fri
Setting 3: Sat - Sun
Setting 4: Monday
Setting 5: Tuesday
Setting 6: Wednesday
Setting 7: Thursday
Setting 8: Friday
Setting 9: Saturday
Setting 10: Sunday
n
S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection
Sets the action that occurs when sequence timers 1 to 4 are active.
No. Name Setting Range Default
S2-04 Sequence Timer 1 Selection 0 to 2 0
S2-09 Sequence Timer 2 Selection 0 to 2 0
S2-14 Sequence Timer 3 Selection 0 to 2 0
5.12 S: Special Parameters
188
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
Przeglądanie stron 187