No. Name Setting Range Default
Z2-05 Digital Input 5 Function Select 0 to 36 25
Z2-06 Digital Input 6 Function Select 0 to 36 0
Z2-07 Digital Input 7 Function Select 0 to 36 0
Z2-08 Digital Input 8 Function Select 0 to 36 29
n
Bypass Digital Input Terminal Settings
Table 5.28 Bypass Digital Input Terminal Settings
Setting Function Page
0
<1>
Unused (Available for Serial Comms)
Note: Multiple digital input terminals can
be programmed for “Unused
(Available for Serial Comms)”
(Z2-0o = 0). The drive will run only
when all digital inputs programmed
for “0” are active. This feature
applies to settings 0 and 22. Set all
other selections only once in
parameters Z2-01 to Z2-08.
207
3 DRV Multi-Function Input S3 (H1-03 Setting) 207
4 DRV Multi-Function Input S4 (H1-04 Setting) 207
5 DRV Multi-Function Input S5 (H1-05 Setting) 207
6 DRV Multi-Function Input S6 (H1-06 Setting) 207
7 DRV Multi-Function Input S7 (H1-07 Setting) 207
21 Run (AUTO Mode) 207
22
<1>
Run Enable (Safety)
Note: Multiple digital input terminals can
be programmed for “Run Enable
(Safety)” (Z2-0o = 22) in bypass
controller software versions
VST800298 and later. The drive will
run only when all digital inputs
programmed for “22” are active.
This feature applies to settings 0 and
22. Set all other selections only once
in parameters Z2-01 to Z2-08.
208
Setting Function Page
23 Run Interlock (BAS) 208
24 Remote Transfer to Bypass 208
25 Smoke Purge Bypass Run to Destruction 208
26
Smoke Purge Drive Run to Destruction at Smoke
Purge Preset Speed
208
27 Motor OR Select 208
28 Motor AND Select 208
29 Motor 1 Overload Contact 208
30 Motor 2 Overload Contact 208
31 HAND Select 208
32 AUTO Select 208
33 DRIVE/BYPASS Select 208
34 Fault Reset 208
35 External Fault (EF0) 208
36 External Fault (EFB) 208
<1> Can be set to multiple digital input parameters simultaneously in bypass controller software versions VST800298 and later.
Setting 0: Unused (Available for Serial Comms)
Note:
Multiple digital input terminals can be programmed for “Unused (Available for Serial Comms)” (Z2-0o = 0). The drive will run only when
all digital inputs programmed for “0” are active. This feature applies to settings 0 and 22. All other selections should only be set once in
parameters Z2-01 to Z2-08.
Setting 3: DRV Multi-Function Input S3 (H1-03 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151 for available H1-03 multi-function input settings.
Setting 4: DRV Multi-Function Input S4 (H1-04 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151 for available H1-04 multi-function input settings.
Setting 5: DRV Multi-Function Input S5 (H1-05 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151 for available H1-05 multi-function input settings.
Setting 6:DRV Multi-Function Input S6 (H1-06 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151 for available H1-06 multi-function input settings.
Setting 7: DRV Multi-Function Input S7 (H1-07 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151 for available H1-07 multi-function input settings.
Setting 21: Run (AUTO Mode)
Starts and stops the bypass when Z1-08 is set to 1.
5.15 Z: Bypass Parameters
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
207