Point
No.
Point
Type
Point Name
Factory
Default
(SI Units)
Engr. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Z1000
Parameter
{28} LDI
LOC.REM
MON
REMOTE – 1 0 LOCAL REMOTE UB-05
{29} LDO DAY.NGT DAY – 1 0 NGT DAY –
30 LAO
CURRENT
LMT
0 AMPS (A)
0.01/0.1
<1>
0 – – E2-01
31 LAO
ACCEL
TIME
0 SEC 0.1 0 – – C1-01
32 LAO
DECEL
TIME
0 SEC 0.1 0 – – C1-02
33 LDO
LOCK
PANEL
UNLOCK – 1 0 LOCK UNLOCK –
35
<3>
LDO
RUN
ENABLE
STOP – 1 0 ENABLE STOP Bypass DI-2
36 LAO
STALL PRE
RN
90 PCT 1 30 – – L3-06
37 LAO
STALL PRE
AC
120 PCT 1 0 – – L3-02
38 LAO
FREQ UP
LIM
100 PCT 0.1 0 – – d2-01
39 LAO
FREQ LOW
LIM
0 PCT 0.1 0 – – d2-02
{40} LDI
MULTI OUT
1
OFF – 1 0 ON OFF
UB-03 (Bit 6)
Bypass DO-7
{41} LDI
MULTI OUT
2
OFF – 1 0 ON OFF
UB-03 (Bit 7)
Bypass
DO-08
{42} LDI
MULTI OUT
3
OFF – 1 0 ON OFF
UB-03 (Bit 8)
Bypass DO-9
{43} LDI
SAFETY
ILOCK
OFF – 1 0 ON OFF UB-05 (Bit 7)
{44}
<4>
LDO MF INP 1 OFF – 1 0 ON OFF Bypass DI-3
{45}
<4>
LDO MF INP 2 OFF – 1 0 ON OFF Bypass DI-4
{46}
<4>
LDO MF INP 3 OFF – 1 0 ON OFF Bypass DI-5
{47}
<4>
LDO MF INP 4 OFF – 1 0 ON OFF Bypass DI-6
{48}
<4>
LDO MF INP 5 OFF – 1 0 ON OFF Bypass DI-7
49 LAO
JUMP FREQ
1
0 HZ 0.1 0 – – d3-01
50 LAO
JUMP FREQ
2
0 HZ 0.1 0 – – d3-02
51 LAO
JUMP FREQ
3
0 HZ 0.1 0 – – d3-03
52 LAO
JUMP FREQ
BW
0 HZ 0.1 0 – – d3-04
53 LAO
NUM
AUTOSTRT
0 – 1 0 – – L5-01
54 LAO
POWER
LOSS RT
0.1 SEC 0.1 0 – – L2-02
55 LAO
RUN OP
MODE
1 – 1 0 – – Z1-08
56 LAO
REF OP
MODE
1 – 1 0 – – Z1-07
57 LAO
OPER DISP
MD
0 – 1 0 – – o1-03
{58} LDI
MF IN 1
MON
OFF – 1 0 ON OFF
UB-02 (Bit 2)
Bypass DI-3
{59} LDI
MF IN 2
MON
OFF – 1 0 ON OFF
UB-02 (Bit 3)
Bypass DI-4
E.4 APOGEE FLN Point List Summary
410
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual