9.7 Send Message Function (MSG-SND)
9-21
9.7.2 Input
EXCUTE (Send Message Execution Command)
When the command becomes "ON", the message is sent.
ABOUT (Send Message Forced Interruption Command)
This command forcibly interrupts the sending of the message. This has priority over EXECUTE
(send message forced interruption command).
DEV-TYP (Transmission Device Type)
Designates transmission device type.
PRO-TYP (Transmission Protocol)
Designates transmission protocol. In non-procedural transmission, a response is not received
from the other station.
MEMOBUS : Setting = 1
Non-procedural : Setting = 2
CIR-NO (Circuit No.)
Designate the Circuit No.
CPU Module = 1, 2, 215IF = 1 to 8, 217IF = 1 to 24, 218IF = 1 to 8, SVB-01 = 1 to 16
CH-NO (Channel No.)
Designate the channel No. of the transmission unit. However, the channel number should be set
so as not to be duplicated on a single line.
CPU Module = 1, 215IF = 1 to 13, 217IF = 1, 218IF = 1 to 10, SVB-01 = 1 to 8
PARAM (Set Data Head Address)
The head address of the set data is designated. For details of the set data refer to
5.5.1."Parameters".
BUSY (In Process)
Indicates that the process is being executed. Keep EXECUTE set to "ON".
COMPLETE (Completion of Process)
Becomes "ON" for only 1 scan upon normal completion.
ERROR (Occurrence of Error)
Becomes "ON" for only 1 scan upon occurrence of error. Refer to PARAM00 and PARAM 01
of 5.5.4.