9.8 Receive Message Function (MSG-RCV)
9-28
CH-NO (Channel No.)
Designate the channel No. of the transmission unit. However, the channel number should be set
so as not to be duplicated on a single line.
CPU Module = 1, 215IF = 1 to 13, 217IF = 1, 218IF = 1 to 10, SVB-01 = 1 to 8
PARAM (Setting Data Head Address)
The head address of the set data is designated. For details of the set data refer to
5.6.1."Parameters".
9.8.3 Output
BUSY (In Process)
Indicates that the process is being executed. Keep EXECUTE set to "ON".
COMPLETE (Completion of Process)
Becomes "ON" for only 1 scan upon normal completion.
ERROR (Occurrence of Error)
Becomes "ON" for only 1 scan upon occurrence of error. Refer to PARAM00 and PARAM01 of
5.6.1."Parameters".