2.2 Operation Sequence for Managing Parameters Using a Controller
2-9
2.2 Operation Sequence for Managing Parameters Using a
Controller
When the parameters are managed by a controller, the parameters are automatically transmitted from the con-
troller to the SERVOPACK when the power is turned ON. Therefore, the settings of SERVOPACK do not
need to be changed when the SERVOPACK is replaced.
∗ If the connection cannot be released normally, send DISCONNECT command for 2 or more communications cycles,
and then send CONNECT command.
Procedure Operation Command to Send
1 Turn on the control and main circuit power supplies. NOP
2 Reset the previous communications status.
DISCONNECT
*
3 Establish communications connection and starts WDT count. CONNECT
4 Check information such as device ID. ID_RD
5 Get device setting data such as parameters. PRM_RD, ADJ
6 Set the parameters required for device. PRM_WR
7 Enable the parameter settings (Setup). CONFIG
8 Turn the encoder power supply to the position data. SENS_ON
9 Turn the servo on. SV_ON
10 Start operation. –
11 Turn the servo off. SV_OFF
12 Disconnect the communications connection. DISCONNECT
13 Turn the control and main circuit power supplies. –