2.1 LED Indicators and Switch Settings
2.1.4 Switch Settings
2-4
2.1.4 Switch Settings
Both the DIP switch and rotary switches set the operating conditions for the SVB-01 Module. Use the default settings
when using the Module in Master Mode.
( 1 ) DIP Switch
SIZE and SPD are valid only in Slave Mode. They will be ignored in Master Mode.
Setting Example
Name Status Operating Mode Default Setting Details
-
ON Reserved.
OFF
Keep turned OFF.
OFF Reserved.
M/S
ON Slave Mode
OFF
Select Master or Slave Mode.
OFF Master Mode
SIZE
ON 17 bytes
OFF
Select the number of send bytes.
Valid only in Slave Mode.
OFF 32 bytes
SPD
ON 4 Mbps
OFF
Select the baud rate.
Valid only in Slave Mode.
OFF 10 Mbps
Communication
Interface
Link
Communication
Switch Settings
MECHATROLINK-I
17-byte
MECHATROLINK-II
17-byte
32-byte
OFF
ON
SPD
SIZE
M/S
OFF
ON
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF